Commissioning
Using the keypad XT EMZ9371BC − Vector control
7
EDK82EV113 DE/EN/FR 8.1
137
L
Switch−on sequence Note
8. Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
9. Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f
[ H z ]
f
2
C 0 0 1 1
f
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
+t
ir
@
C0011
f
2
* f
1
t
ir
= acceleration time wanted
11. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+t
if
@
C0011
f
2
* f
1
t
if
= deceleration time wanted
12. Set the control mode "Vector control" (C0014 =
4)
Lenze setting: Linear V/f characteristic control
(C0014 = 2)
d ABbc
p
SHPRG
Para
Code
Menu
0014
00
4
Vector-Ctrl
9371BC008
13. Enter the motor data See motor nameplate
A Rated motor speed (C0087)
Lenze setting: 1390 rpm
B Rated motor current (C0088)
Lenze setting: Depending on the controller
Enter the value for the motor
connection type (star/delta) selected!
C Rated motor frequency (C0089)
Lenze setting: 50 Hz
D Rated motor voltage (C0090)
Lenze setting: Depending on the controller
Enter the value for the motor
connection type (star/delta) selected!
E Motor−cos (C0091)
Lenze setting: Depending on the controller
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com