Commissioning
The most important codes for commissioning
7
EDK82EV113 DE/EN/FR 8.1
143
L
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0002*
uSEr
(cont.)
Saving of own
settings
9
PAR1 ð Own settings
You can save your own basic settings
for a controller (e.g. machine delivery
status):
1. Ensure that parameter set 1 is
active
2. Controller inhibit
3. Set C0003 = 3, acknowledge with
4. Set C0002 = 9, acknowledge with
, to save your own basic
settings
5. Set C0003 = 1, acknowledge with
6. Enable the controller.
C0002*
uSEr
(cont.)
Loading/copying
of your own
basic settings
Using this function, PAR1 can be
copied to parameter sets PAR2 ...
PAR4
5
Own settings ð PAR1
Restorage of own basic setting in the
selected parameter set
6
Own settings ð PAR2
7
Own settings ð PAR3
8
Own settings ð PAR4
C0003*
Non−volatile
parameter
saving
1
0 Parameter not saved in EEPROM Data loss after mains disconnection
1 Parameter always saved in EEPROM l Active after every mains
connection
l Cyclic parameter changes via bus
module are not allowed.
3 Own settings saved in EEPROM Subsequently save parameter set 1 as
own basic setting with C0002 = 9