Commissioning
The most important codes for commissioning
7
EDK82EV113 DE/EN/FR 8.1
147
L
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0014
Operating mode 2
2 V/f characteristic control V ~ f
(Linear characteristic with constant V
min
boost)
l Commissioning without motor
parameter identification possible
l Benefit of identification with
C0148:
– Improved smooth running at low
speed
– V/f rated frequency (C0015) and
slip (C0021) are calculated and
stored. They do not have to be
entered
3 V/f characteristic control V ~ f
2
(Square−law characteristic with constant
V
min
boost)
4 Vector control
For initial selection enter the motor
data and identify the motor
parameters with C0148
Otherwise commissioning is not
possible
5 Sensorless torque control with speed
limitation
l Torque setpoint via C0412/6
l Speed limitation via setpoint 1
(NSET1−N1), if C0412/1 is assigned, if
not via max. frequency (C0011)
C0015
uSEr
V/f rated
frequency
50.00 7.50 {0.02 Hz} 960.00 l C0015 is calculated and stored
under C0148 when the motor
parameters are identified
l Settings applies to all possible
mains voltages
C0016
uSEr
U
min
boost
à
0.00 {0.01 %} 40.00 àDepending on the controller
Setting applies to all mains voltages
permitted
C0034*
uSEr
Setpoint
selection range
Standard–I/O
(X3/8)
−34−
Observe the switch position of the
function module!
0
0 Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1 Current 4 ... 20 mA Changing the direction of rotation is
only possible with a digital signal.
2 Bipolar voltage −10 V ... +10 V l Minimum output frequency (C0010)
not effective
l Individual adjustment of offset and
gain
3 Current 4 ... 20 mA open−circuit monitored TRIP Sd5, if I < 4 mA
Changing the direction of rotation is
only possible with a digital signal.