Fault detection and elimination
Fault messages
8
EDK82EV113 DE/EN/FR 8.1
153
L
Error messages at the keypad or in the parameter setting program Global Drive
Control
Keypad PC
1)
Error Cause Remedy
noer
0 No fault − −
ccr
71 System fault
Strong interferences on control cables Shield control cables
Ground or earth loops in the wiring
ce0
61 Communication fault to
AIF
(configurable in C0126)
Faulty transmission of control
commands via AIF
Insert the communication module into the
hand terminal
ce1
62 Communication fault to
CAN−IN1 with Sync
control
CAN−IN1 object receives faulty data or
communication is interrupted
l Plug−in connection − bus module ó
Check FIF
l Check transmitter
l Increase monitoring time under C0357/1
if necessary
ce2
63 Communication error to
CAN−IN2
CAN−IN2 object receives faulty data or
communication is interrupted
l Plug−in connection − bus module ó
Check FIF
l Check transmitter
l Increase monitoring time under C0357/2
if necessary
ce3
64 Communication error to
CAN−IN1 with event or
time control
CAN−IN1 object receives faulty data or
communication is interrupted
l Plug−in connection − bus module ó
Check FIF
l Check transmitter
l Increase monitoring time under C0357/3
if necessary
ce4
65 BUS−OFF
(many communication
faults occurred)
Controller has received too many
incorrect telegrams via the system
bus and has been disconnected
l Check whether bus terminator available
l Check screen contact of the cables
l Check PE connection
l Check bus load, if necessary, reduce the
baud rate
ce5
66 CAN Time−Out
(configurable in C0126)
For remote parameter setting via
system bus (C0370):
Slave does not answer.
Communication monitoring time
exceeded.
l Check system bus wiring
l Check system bus configuration
For operation with module in FIF:
Internal fault
Contact Lenze
ce6
67 Function module
system bus (CAN) on
FIF has set "Warning"
or "BUS−OFF"
(configurable in C0126)
CAN controller sets "Warning" or "BUS
OFF"
l Check whether bus terminator available
l Check screen contact of the cables
l Check PE connection
l Check bus load, if necessary, reduce the
baud rate
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com