Safety instructions
1
EDK82EV113 DE/EN/FR 8.1
89
L
Controller protection
l All pluggable connection terminals must only be connected or disconnected when
no voltage is applied!
l Cyclic connection and disconnection of the supply voltage can overload and
destroy the input current limitation of the controller:
In case of cyclic mains switching over a longer period of time three minutes have
to pass between two starting operations!
Motor protection
l Depending on the controller settings, the connected motor can be overheated:
For instance, longer DC−braking operations.
Longer operation of self−ventilated motors at low speed.
Controller/system protection
l Drives can reach dangerous overspeeds (e.g. setting of inappropriately high field
frequencies):
The controllers do not offer any protection against these operating conditions. For
this, use additional components.
l Contactors in the motor cable Switching with inhibited controller only.
If contactors in the motor cable are switched with the controller enabled,
monitoring functions of the controller can be activated.
the controller can be destroyed under unfavourable operating conditions.
Warnings!
l The device has no overspeed protection.
l Must be provided with external or remote overload protection.
l Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum (240 V devices) or 500 V maximum
(400/500 V devices) resp.
l Use 60/75 °C or 75 °C copper wire only.
l Shall be installed in a pollution degree 2 macro−environment.