Safety instructions
1
EDK82EV113 DE/EN/FR 8.1
89
L
Controller protection
l All pluggable connection terminals must only be connected or disconnected when
no voltage is applied!
l Cyclic connection and disconnection of the supply voltage can overload and
destroy the input current limitation of the controller:
– In case of cyclic mains switching over a longer period of time three minutes have
to pass between two starting operations!
Motor protection
l Depending on the controller settings, the connected motor can be overheated:
– For instance, longer DC−braking operations.
– Longer operation of self−ventilated motors at low speed.
Controller/system protection
l Drives can reach dangerous overspeeds (e.g. setting of inappropriately high field
frequencies):
– The controllers do not offer any protection against these operating conditions. For
this, use additional components.
l Contactors in the motor cable Switching with inhibited controller only.
If contactors in the motor cable are switched with the controller enabled,
– monitoring functions of the controller can be activated.
– the controller can be destroyed under unfavourable operating conditions.
Warnings!
l The device has no overspeed protection.
l Must be provided with external or remote overload protection.
l Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum (240 V devices) or 500 V maximum
(400/500 V devices) resp.
l Use 60/75 °C or 75 °C copper wire only.
l Shall be installed in a pollution degree 2 macro−environment.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com