Complete motec wiring according to EMC
requirements
5
MA8200MOT DE/EN/FR 3.0
Conditions for trouble-free operation:
l
Except for the mains cable, use shielded cables only.
l
The shield must be carefully connected to PE (see below).
l
Connect motor and mains PE conductors to separate PE terminals.
Shield connection
1. Prepare cable.
1
2
2. Insert cable binder.
0
3
4
3. Lay cable into the binder and
tighten the binder. The shield
must be tightly connected to the
shield sheet.
4
5
0
Mains cable
1
Mains connection L1, L2/N
2
PE connection - mains cable
3
Shield connection - control cable: fix the shield with cable binder to the sheet
4
Shielded control cable
5
Function module
PES HF shield connection by PE connection to the shield