Wiring for wall mounting according to EMC
requirements
9
MA8200MOT DE/EN/FR 3.0
Conditions for trouble-free operation:
l
Except for the mains cable, use shielded cables only
l
The shield must be carefully connected to PE (see below).
l
Separate control and mains cables from motor cable!
l
Connect motor and mains PE conductors to separate PE terminals.
Shield connection
1. Prepare cable
1
2
3
4
4
2. Insert cable binders
0
4
5
6
7
8
9
3. Lay cable into the binder and
tighten the binder. The shield
must be tightly connected to the
shield sheet.
8
9
0
Mains cable
1
Mains connection L1, L2/N
2
PE connection - mains cable
3
Motor connection U, V, W
4
Shield connection - motor cable: fix the shield with cable binder to the sheet
5
PE connection - motor cable
6
Shielded motor cable
7
Shield connection - control cable: fix the shield with cable binder to the sheet
8
Shielded control cable
9
Function module
PES HF shield connection by PE connection to the shield