Parameter setting / User menu
18
MA8200MOT DE/EN/FR 3.0
The user menu - The 10 most important drive parameters
After mains switching or plugging in the keypad during operation, the 10 codes defined to be the most important
in the user menu (Code C0517) are available immediately.
In factory setting, the user menu lists all parameters required for a standard application with linear
V/f-characteristic control:
Code Name Lenze setting
C0050 Output frequency Display: Output frequency without slip compensation
C0034 Setpoint selection range -0-
Standard-I/O X3/8: 0 ... 5 V/ 0 ... 10 V/ 0 ... 20 mA
Application-I/O
X3/1U: 0 ... 5 V/ 0 ... 10 V
X3/2U: 0 ... 5 V/ 0 ... 10 V
C0007 Fixed configuration of digital -0-
E4 E3 E2 E1
u
inputs
CW/CCW DCB JOG2/3 JOG1/3
CW/CCW rotation DC-injection
brake
Selection of fixed setpoints
C0010 Minimum output frequency 0.00 Hz
C0011 Maximum output frequency 50.00 Hz
C0012 Acceleration time main setpoint 5.00 s
C0013 Deceleration time main setpoint 5.00 s
C0015 V/f rated frequency 50.00 Hz
C0016 V
min
boost Depending on the inverter type
C0002 Parameter set transfer See code table (
&
20)
The user menu can be changed according to your requirements under C0517.
Note!
l
Change to the menu
DMM
to enable code activation.
l
Use C0002 ”Parameter set transfer” to easily transfer configurations from one controller
to the other or to reset the controller to Lenze settings (in case you lose the ”red thread”
during parameter setting).