Technical data
Rated data
Overview
4
24
EDS84ABD302 EN 4.0
4.2 Rated data
4.2.1 Overview
Input data
Basis of the data
Mains
Voltage
U
LN
[V]
Voltage range
U
LN
[V]
Frequency range
f[Hz]
1/N/PE AC 230 180-0%...264+0% 45-0%...65+0%
3/PE AC 400 320-0%...440+0% 45-0%...65+0%
3/PE AC 500 400-0%...550+0% 45-0%...65+0%
Voltage Frequency Current [A]
Number of
phases
Type [V] [Hz] max. +45 °C
c
max. +55 °C
c
E84AVBxx2512 230 50/60 3.4 2.6 1
E84AVBxx3712 230 50/60 5.1 3.8 1
E84AVBxx5512 230 50/60 6.7 5.0 1
E84AVBxx7512 230 50/60 8.8 6.6 1
E84AVBxx1122 230 50/60 12 9.0 1
E84AVBxx1522 230 50/60 13.7 10.3 1
E84AVBxx2222 230 50/60 22.0 18.4 1
E84AVBxx3714 400/500 50/60 1.8/1.5 1.4/1.1 3
E84AVBxx5514 400/500 50/60 2.3/2.0 1.7/1.5 3
E84AVBxx7514 400/500 50/60 3.2/2.7 2.4/2.0 3
E84AVBxx1124 400/500 50/60 4.2/3.6 3.2/2.7 3
E84AVBxx1524 400/500 50/60 4.7/4.1 3.5/3.1 3
E84AVBxx2224 400/500 50/60 6.2/5.4 4.7/4.1 3
E84AVBxx3024 400/500 50/60 10.2/7.8 7.7/5.9 3
c Ambient temperature in the control cabinet, switching frequency 2 and 4 kHz, operation without mains choke