EasyManua.ls Logo

Lenze 8400 BaseLine C - Analog Input

Lenze 8400 BaseLine C
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Control terminals
Analog input
4
41
EDS84ABD302 EN 4.0
4.5.2 Analog input
Labelling Feature Rated value
A1U
GND
Input
0 ... +10 V with DC voltage
0 ... +5 V DC (0 ... +20 mA)
1 ... +5 V DC (+4 ... +20 mA)
Input resistance >50kΩ with DC voltage
250 Ω (external) with DC current
Input voltage in case of open circuit Display ”0” (U < 0.2 V, absolute)
Sampling frequency 1kHz(1ms)
Accuracy ± 0.1 V
Electric strength of external voltage ± 15 V, permanent
A/D converter 10 bit resolution
Error 1 digit 0.1 % with regard to final value