Electrical installation
Devices i n the power range 0.25 ... 2.2 kW (1/N/PE AC 230 V)
Terminal assignment of the power connections
6
61
EDS84ABD302 EN 4.0
6.3.2 Terminal assignment of the power connections
Strip cables
X105
84BLMOTL001_a
U, V, W PE
b c e a d
[mm] [mm]
E84AVBxE2512
75
130 7 160 7
E84AVBxE3712
E84AVBxE5512
95 150 7 180 7
E84AVBxE7512
E84AVBxE1122
E84AVBxE1522
E84AVBxE2222
How to proceed:
1. Strip motor cable as specified.
2. Fold back shield of motor c able over the cable sheath. Keep unshielded cable ends as
short as possible.
3. Fix shield on the cable sheath (e.g. using a heat-shrinkable tube).
4. Fasten wire end ferrule to PE cable.
– The other cables may be wired without using wire end ferrules.
5. Connect motor cable shield to PE terminal of inverter.
– For strain relief of the cables, additional measures are required.