Electrical installation
Devices i n the power range from 0.37 to 3 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
67
EDS84ABD302 EN 4.0
6.4.2 Terminal assignment of the power connections
Strip cables
X105
84BLMOTL001_a
U, V, W PE
b c e a d
[mm] [mm]
E84AVBxE3714
95
150 7 180 7
E84AVBxE5514
E84AVBxE7514
E84AVBxE1124
E84AVBxE1524
E84AVBxE2224
E84AVBxE3024
How to proceed:
1. Strip motor cable as specified.
2. Fold back shield of motor c able over the cable sheath. Keep unshielded cable ends as
short as possible.
3. Fix shield on the cable sheath (e.g. using a heat-shrinkable tube).
4. Fasten wire end ferrule to PE cable.
– The other cables may be wired without using wire end ferrules.
5. Connect motor cable shield to PE terminal of inverter.
– For strain relief of the cables, additional measures are required.