Technical data
Rated data
Operation at rated mains voltage 230 V
4
27
EDS84ABD302 EN 4.0
Output currents [A] at switching frequency
2kHz 4kHz 8kHz 16 kHz
Type I
aN2
I
aM2
I
aN4
I
aM4
I
aN8
I
aM8
I
aN16
I
aM16
E84AVBxx2512 1.7 3.4 1.7 3.4 1.7 3.4 1.1 2.2
E84AVBxx3712 2.4 4.8 2.4 4.8 2.4 4.8 1.6 3.2
E84AVBxx5512 3.0 6.0 3.0 6.0 3.0 6.0 2.0 4.0
E84AVBxx7512 4.0 8.0 4.0 8.0 4.0 8.0 2.7 5.4
E84AVBxx1122 5.5 11.0 5.5 11.0 5.5 11.0 3.7 7.4
E84AVBxx1522 7.0 14.0 7.0 14.0 7.0 14.0 4.7 9.4
E84AVBxx2222 9.5 19.0 9.5 19.0 9.5 19.0 6.3 12.6
I
aNx
Rated value - continuous output current
I
aMx
Maximum output current (overload current)
z Periodic load change of 3 s with I
aMx
and recovery time of 12 s with 75 % I
aNx
z Can be achieved with the setting ”x kHz fixed/...” in C00018
Switching
frequency
When the maximum heatsink temperature is reached, the switching frequency
is reduced to 4 kHz.
With the setting ”x kHz var./...” in C00018, the switching frequency is reduced
dynamically.
z At 16 kHz and Ia > 100 % x IaN8 to 8 kHz
z At8kHzandIa>150%xIaN8to4kHz
Fuses and cable cross-sections
Operation without external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c d L1, N - laying system e L1, N
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84AVBxx2512 C10 10 1.5 - - 10 14
≥ 30
E84AVBxx3712 C10 10 1.5 - - 10 14
E84AVBxx5512 C16 16 1.5 - - 12 14
E84AVBxx7512 C16 16 1.5 - - 15 14
E84AVBxx1122 C20 20 2.5 - - 20 12
E84AVBxx1522 C25 25 4
4)
- - 20 10
E84AVBxx2222 C32 32 6
4)
- - 35 10
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4).
The cable-cross sections apply under the following conditions: Use of PVC-insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, two loaded cores. Smaller cable
cross-sections are not permissible for technical reasons.
2)
Use UL-approved cable, fuses, and fuse holders only.
UL fuse: voltage ≥ 240 V, tripping characteristic ”H”, ”K5” or ”CC”.
The cable cross-sections apply under the following conditions: conductor temperature < 75 °C, ambient temperature
< 45°C. Smaller cable cross-sections are not permissible for technical reasons.
3)
Pulse-current sensitive or universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
4)
only with pin-end connector
c Circuit breaker
d Fuse
e Fuse
Observe national and regional regulations