Commissioning
Test commissioning
Test commissioning with keypad control
7
89
EDS84ABD302 EN 4.0
4. Set keypad control
-0-
_
_
`
_
`
....
C002
0020
-3-
0000
0000
`
`
`
`
`
_
`
....
84BLMEN001
z Select menu -3- (quick commissioning with integrated keypad)
z Press ”Enter” key
z Set C007 code
z Press ”Enter” key
z Set value ”20”
z Press ”Enter” key
5. Enable controller:
Set terminal X4/RFR to HIGH-Potential (reference: X4/12I).
6. Vary the motor speed with the integrated keypad or by defining different fixed
setpoints:
Internal Keypad Code Subcode Motor speed
_
C00728 3 Counter-clockwise rotation:
-199.9 % .... 0 (from C00011)
Clockwise rotation
0 ... +199.9 % (from C00011)
C00051 - Observe
z the actual speed value:
C00051
z appearing messages 92
7. Save the settings with mains failure protection by entering the value ”1” in code
C002, subcode 7.