Technical data
Communication time
18
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.3 Communication time
The communication time defines the time between the start of a request and the arrival of the
corresponding response.
The communication times in an AS-i network depend on the ...
processing time in the inverter;
telegram runtime (baud rate / telegram length);
nesting depth of the network.
Processing time in the inverter
There are no interdependencies between parameter data and process data.
Data Processing time
Process data approx. 2 ms
+ 0 ... 1 ms
+ 1 ... x ms
Update cycle
Processing time in the module
Application task runtime of the use technology application
(tolerance)
Parameter data approx. 30 ms + a tolerance of 20 ms (typically)
For some codes, the processing time may be longer (see software manual/
»Engineer« online help "Inverter Drives 8400 motec").