Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013 47
Parameter data transfer
CTT2: Write code number
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.4 CTT2: Write code number
• Acyclic write request from master to slave:
• Response from slave to master is OK:
• Response from slave to master has failed:
Byte Contents / value
0 CTT2: Code
•Index 0x13 (19): Acyclic write request
1 CTT2: Index
•Index 0x11 (17): Write code number
2 CTT2: Number of bytes
• 0x4 (4)
3Index high
byte
Index = 0x5FFF (code of the inverter)
4Index low
byte
5Subindex
6 Reserved
Byte Contents / value
0 CTT2: Code
•Index 0x53 (83): Acyclic write request is OK.
• Code number was written.
Byte Contents / value
0 CTT2: Code
•Index 0x93 (147): Acyclic write request is not OK.
1 CTT2: Standard error code
CTT2: Standard error codes
( 51)
2Error code (MSB)
3Error code
4Error code
5Error code (LSB)
CTT2: Acyclic device error codes
( 52)