Parameter data transfer
CTT2: Block parameter transfer
50
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.5.2 Write mode
• Acyclic write request from master to slave:
• Response from slave to master is OK:
• Response from slave to master has failed:
• After the acyclic write request (index 0x13 (19)) has failed, the master sends error codes.
• Then the write request from master to slave with the index 0x29 (41) is repeated.
• The slave sends the parameter values in code C13213/1...16
again.
Byte Contents / value
0 CTT2: Code
•Index 0x13 (19): Acyclic write request
1 CTT2: Index
•Index 0x28 (40): Write parameter
2 CTT2: Number of bytes
• 0x41 (65)
3 Reserved
4 ... 7 Double word 1
• Value of the parameter in code C13213/1
... ...
64 ... 67 Double word 16
• Value of the parameter in code C13213/16
Byte Contents / value
0 CTT2: Code
•Index 0x53 (83): Acyclic write request is OK.
• All the parameters were written.
Byte Contents / value
0 CTT2: Code
•Index 0x93 (147): Acyclic write request is not OK.
• Read exception list (index 0x29 (41))
1 CTT2: Standard error code
CTT2: Standard error codes
( 51)
2Error code (MSB)
3Error code
4Error code
5Error code (LSB)
CTT2: Acyclic device error codes
( 52)
Note!
Faulty writing of parameter sets can change single parameters.