Adjusting the motor
Motor temperature monitoring with KTY
6.6
6.6.4
6.6−11
EDSVF9383V EN 7.1−04/2012
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0594 MONIT SD6 3
0 TRIP
Activation of the motor
temperature monitoring with KTY
at X8
l Use C0594 = 0 or 2 to activate
monitoring
l In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated
l Configuration of the response
when exceeding the motor
temperature
Fixed operating temperature
in C0583
Variable operating
temperature in C0584
6.6−10
See System
Manual
(extension)
2 Warning
3 Off
C1190 Motor PTC
selection
0
Temperature characteristic for PTC
thermistors
l Selection of the characteristic
for PTC thermistors at X7 or X8
for detecting the motor
temperature
6.6−10
0 Standard Characteristic for PTC thermistors
in Lenze motors
1 Characteristic Characteristic for
application−specific PTC
thermistors
C1191 Temperature
characteristic
0 {1 °C} 255 Temperature range for PTC
thermistors
l Define temperature points on
the characteristic for PTC
thermistors
1 Temperature 1 100 Temperature point 1
2 Temperature 2 150 Temperature point 2
C1192 Resistance
characteristic
0 {1 W} 3000 Resistance characteristic for PTC
thermistors
l Define resistance points on the
characteristic for PTC
thermistors
1 Resistance 1 1670 Resistance point 1
2 Resistance 2 2225 Resistance point 2