Adjusting the motor
Motor temperature monitoring with KTY
6.6
6.6.4
6.6−12
EDSVF9383V EN 7.1−04/2012
Note!
ƒ In the Lenze setting, the motor temperature monitoring is
switched off!
ƒ If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!
Use C0594 = 0 or C0594 = 2 to activate the motor temperature monitoring
via X8. In addition, the connection is monitored for short circuit and
interruption.
1. Connecting the monitoring circuit of the motor to X8/5 and X8/8.
2. Setting controller reaction to short circuit or interruption of the
connection:
C0594 = 3: Monitoring is switched off.
C0594 = 0: TRIP error message (display of keypad: Sd6 )
C0594 = 2: Warning signal (display of keypad: Sd6 !)
Monitoring with a fixed operating temperature (150 °C)
1. Set response of the controller:
C0583 = 3: temperature monitoring of the motor switched off.
C0583 = 0: TRIP error message (keypad display: OH3 )
C0583 = 2: warning signal (keypad display: OH3 !)
Monitoring with a variable operating temperature (45...150 °C)
1. Set the operating temperature in C0121.
2. Set response of the controller:
C0584 = 3: temperature monitoring of the motor switched off.
C0584 = 2: warning signal (keypad display: OH7 !)
Activation
Adjustment