Configuration
Code table
8
8.5
8.5−17
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0173
UG limit 1
Check during commissioning and
adapt, if necessary!
All controllers in the system must
have the same threshold!
l Adaptation of UG thresholds
l Only display in case of the
variants for 400 V mains
(EVF93xx−EV, EVF93xx−EVV030,
EVF93xx−EVV060,
EVF93xx−EVV110):
C0173 = 1
OU = 700 ... 685 V
12−1
See System
Manual
(extension)
Mains LU OU
0 < 400 V 285 V 770 ... 755 V
Device with or without brake
transistor
1 400 V 285 V 770 ... 755 V
2 460 V 328 V 770 ... 755 V
3 480 V 342 V 770 ... 755 V Device without brake transistor
4 480 V 342 V 800 ... 785 V
Device with brake transistor
5 500 V 342 V 900 ... 885 V
C0174 BR Limit 3
Display of the brake transistor
thresholds
Check during commissioning and
adapt, if necessary!
All controllers connected to the
bus must have the same
threshold!
12−1
See System
Manual
(extension)
Mains U
BR
OU
0 400 V 685 V 700 V Only display in case of the variants
for 400 V mains (EVF93xx−EV,
EVF93xx−EVV030,
EVF93xx−EVV060,
EVF93xx−EVV110)
1 400 V / 460 V 755 V 770 V
Only in case of the variants for
400 V/500 V mains
(EVF93xx−EVV210,
EVF93xx−EVV240,
EVF93xx−EVV270,
EVF93xx−EVV300)
2 480 V 785 V 800 V
3 500 V 885 V 900 V
C0178 Op timer {s} Display only
Total time of the controller enable
(X5/28 = HIGH)
C0179 mainstimer {s} Display only
Total time of mains "ON"
C0182 Ti S−shaped 20.00 0.01 {0.01 s} 50.00 Integration time of S−shaped ramp
function generator, function block
NSET
l C0182 = 0.00: ramp function
generator operates linearly
l C0182 > 0.00: ramp function
generator operates in an
S−shape (without jerk)
See System
Manual
(extension)