Configuration
Code table
8
8.5
8.5−38
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0640 Delay T 20.00 0.01 {0.01 s} 50.00 Time constant, function block
PT1−1
l Time period by which the
output of analog signal is
delayed
See System
Manual
(extension)
C0641
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block PT1−1
C0642 DIS: IN −199.99 {0.01 %} 199.99 Function block PT1−1
l Display of the signal linked in
C0641
C0643 Delay T 20.00 0.01 {0.01 s} 50.00 Time constant, function block
PT1−2
l Time period by which the
output of analog signal is
delayed
C0644
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block PT1−2
C0645 DIS: IN −199.99 {0.01 %} 199.99 Function block PT1−2
l Display of the signal linked in
C0644
C0650 DT1−1 gain 1.00 −320.00 {0.01 } 320.00 Gain, function block DT1−1
l Gain of the analog input signal
See System
Manual
(extension)
C0651 Delay T 1.000 0.005 {0.01 s} 5.000 Time constant, function block
DT1−1
l Time period by which the
output of analog signal is
delayed
C0652
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block DT1−1
C0653 Sensibility 1
1 15 bits
Input sensitivity, function block
DT1−1
l According to the setting only
the indicated higher−order bits
are evaluated
2 14 bits
3 13 bits
4 12 bits
5 11 bits
6 10 bits
7 9 bits
C0654 DIS: IN −199.99 {0.01 %} 199.99 Function block DT1−1
l Display of the signal linked in
C0652
C0655 Numerator 1 −32767 {1} 32767 Configuration of conversion factor
with numerator and denominator,
function block CONV5
See System
Manual
(extension)
C0656 Denominator 1 1 {1} 32767
OUT[rpm] + IN[%] @
15000rpm
100%
@
C0655
C0656
C0657
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block CONV5
C0658 DIS: IN −199.99 {0.01 %} 199.99 Function block CONV5
l Display of the signal linked in
C0657
C0661
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block ABS1
l Converts bipolar signals into
unipolar signals
See System
Manual
(extension)
C0662 DIS: IN −199.99 {0.01 %} 199.99 Function block ABS1
l Display of the signal linked in
C0661