Configuration
Code table
8
8.5
8.5−60
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0970
CFG: SET 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MFAIL
l Starting value for the
controlled deceleration in [%]
of C0011
See System
Manual
(extension)
C0971
CFG: FAULT 1000 FIXED0 Selection list 2 Configuration of digital input
signal, function block MFAIL
l HIGH = activates mains failure
control
C0972
CFG: RESET 1000 FIXED0 Selection list 2 Configuration of digital input
signal, function block MFAIL
l HIGH = resets mains failure
control
C0973
CFG: ADAPT 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MFAIL
l Dynamic adaptation of the
proportional gain of U
Gsetl
controller in [%] of C0980
C0974
CFG: CONST 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MFAIL
l Proportional gain of U
Gset
controller in [%] of C0980
C0975
CFG:
THRESHLD
1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MFAIL
l Restart protection when the
value falls below the speed
threshold
l Restart threshold in [%] of
C0011
C0976
CFG: NACT 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MFAIL
l Comparison value for the
restart threshold in [%] of
C0011
l Start for V
2
controller
C0977
CFG: SET 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MFAIL
l Speed starting value for the
deceleration in [%] of C0011
C0978
CFG: DC−SET 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MFAIL
l Setting of the voltage setpoint
on which the DC−bus voltage is
to be kept (100 % = 1000 V)
C0980 MFAIL Vp 0.500 0.001 {0.001} 31.000 Gain V
p
, function block MFAIL
See System
Manual
(extension)
C0981 MFAIL Tn 100 20 {1 ms} 2000 Integral−action time T
n
, function
block MFAIL
C0982 MFAIL Tir 2.000 0.001 {0.001 s} 16.000 Acceleration time T
ir
, function
block MFAIL
C0983 Retrigger T 1.000 0.001 {0.001 s} 60.000 Retrigger time, function block
MFAIL
l After the time has elapsed, the
mains failure control is
terminated