Wiring of the standard device
Control terminals
With function "Safe torque off" deactivated
5
5.5
5.5.4
5.5−8
EDSVF9383V EN 6.0−11/2009
Supply via external voltage source
GND2 +24V+5 V
E5
A2 A3 A4 ST1
ST2
59
39
3k
47k
50mA
50mA
50mA
50mA
X5
28
E1 E2 E3 E4
3k
3k
3k
3k
3k
DC 24 V
(+18 V … +30 V)
X11
K31K32 33 34
S1
+
K
SR
+
–
A1
X3
GND1 GND1
X6
12
3
4
7762
63
242R
1
2
3
4
5
6
100k
100k
100k
100k
3.3nF
AIN1 AIN2
AOUTx
AOUT2
AOUT1
1
3
247
10k 10k
9300vec138
Fig. 5.5−6 Wiring of digital and analog inputs/outputs with function "Safe torque off"
deactivated, given an external voltage source
S1 Controller enable
NO contact or NC contact
Z
Load
Minimum wiring required for operation
Terminal assignment in the Lenze setting: 5.5−9
Note!
Supplying the digital inputs via an external voltage source
enables a backup operation in the case of mains failure. After
switching off the mains voltage, all actual values are continued
to be detected and processed.
ƒ Connect the positive pole of the external voltage source with
X5/59 to establish the backup operation in the event of mains
failure.
ƒ The external voltage source must be able to supply a current
³ 1 A.
ƒ The starting current of the external voltage source is not
limited by the controller. Lenze recommends the use of
voltage sources with current limitation or with an internal
impedance of Z > 1 W.