DC−bus operation
Braking operation in the network
10
10.7
10.7−1
EDSVF9383V EN 6.0−11/2009
10.7 Braking operation in the network
ƒ Controllers EVx9335 ... EVx9383 in variants V270 and V300 are
equipped with an integrated brake transistor.
ƒ Controllers EVx9381 ... EVx9383 in variants V270 and V300 consist of a
master and a slave. Both master and slave contain one brake transistor,
respectively. The braking energy is normally dissipated in equal shares
via master and slave.
ƒ In the DC−bus connection you have to set the switching thresholds of
the brake transistors for all controllers of variants V270 and V300 to
the same value (C0174).
ƒ When the braking energy is low (e. g. operation in generator mode),
you can also use 9352 brake choppers. A simultaneous braking
operation with a 9352 brake chopper and an integrated brake resistor
is not possible due to the different switching thresholds.