DC−bus operation
Fuses and cable cross−sections
DC supply
10
10.4
10.4.2
10.4−2
EDSVF9383V EN 6.0−11/2009
10.4.2 DC supply
A DC supply is only possible for the variants V210, V240, V270, V300.
Stop!
ƒ Only use semiconductor fuses (gRL).
ƒ On principle, fuse DC cables as 2−pole (+U
G
, −U
G
).
9300 vector Installation in accordance with EN 60204−1
Fuse Cable cross−sections
+U
G
, −U
G
PE
Type [A] [mm
2
] [mm
2
]
EVF9335−EVV2xx
EVF9335−EVV300
315
150
2 × 50
1)
95
EVF9336−EVV2xx
EVF9336−EVV300
350
150
2 × 50
1)
95
EVF9337−EVV2xx
EVF9337−EVV300
400
240
2 × 95
1)
95
EVF9338−EVV2xx
EVF9338−EVV300
500
240
2 × 95
1)
150
Master Slave Master Slave Master Slave
EVF9381−EVV2xx
EVF9381−EVV300
350 350
150
2 × 50
1)
150
2 × 50
1)
95 95
EVF9382−EVV2xx
EVF9382−EVV300
400 400
240
2 × 95
1)
240
2 × 95
1)
95 95
EVF9383−EVV2xx
EVF9383−EVV300
500 500
240
2 × 95
1)
240
2 × 95
1)
150 150
1)
Multiple conductor; both conductors must have the same cross−section