Safety engineering
Appendix
Module internal codes
1
129
EDS94AYAE EN 6.0
Index:Data type:Name:Parameter:
C15821 Service code
INTEGER_16 8754
d
= 2232
h
for Lenze service: Currently monitored speed value of ramp monitoring.
Display area
(min. value | unit | max. value) Information
−16000 rpm 16000 Displayed value is only valid if SS1 or SS2 are active
with ramp monitoring.
(From SM301 V1.4)
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15822 Service code
INTEGER_16 8753
d
= 2231
h
for Lenze service: Minimum differences between actual speed value and monitored ramp.
Display area
(min. value | unit | max. value) Information
−16000 rpm 16000 The value is kept until the ramp monitoring is
restarted.
(From SM301 V1.4)
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15890 Current time
UNSIGNED_32 8685
d
= 21ED
h
Relative time for use in logbook.
Display area
(min. value | unit | max. value) Information
0 ms 4294967295
(From SM301 V1.4)
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15891 Log function
UNSIGNED_8 8684
d
= 21EC
h
Setting of the logging behaviour (trigger condition). (From SM301 V1.4)
Selection list Information
0 Logging is active Logging is always active.
1 Logging is stopped Logging is switched off.
2 Stop logging in case of error Logging is stopped if an error occurs.
3 Stop logging in case of STO Logging is stopped if STO occurs.
4 Stop logging in case of SS1 Logging is stopped if SS1 occurs.
5 Stop logging in case of SS2 Logging is stopped if SS2 occurs.
þ Read access þ Write access o Controller inhibit o PLC-STOP o No transfer
C15892 Log time
UNSIGNED_32 8683
d
= 21EB
h
Time of log entry.
Display area
(min. value | unit | max. value) Information
0 ms 4294967295
(From SM301 V1.4)
Subcodes Information
C15892/1 Log time n
C15892/2 Log time n−1
...
C15892/10 Log time n−9
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15893 Log state
BITFIELD_64 8682
d
= 21EA
h
Logged state
Display area
Information
(From SM301 V1.4)
Value is bit−coded Information
Bit 0 STO via SD−In STO was triggered via a safe input.
Bit 1 STO via S−bus STO was triggered via the safety bus.
Bit 2 STO through error STO was triggered through an error.
Bit 3 Reserved