14 Implemented CIP™ objects
14.1 General CIP objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Instance attribute "Status" (attribute 5)
Supported service codes
Attribute
ID
Service Name Data type Value
10 Get Heartbeat Interval USINT Interval between heartbeat messages in
milliseconds
0 ms: No transmission of heartbeat
messages (standard setting)
Bits Name Description
0 Owned The state ’1’ indicates that the device (or an object within the device) has
an owner. Within a master/slave model, the state ’1’ indicates that the
"predefined master/slave connection set" is assigned to a master.
Outside the master/slave model, it means "TBD".
1- Reserved (0)
2 Configured The state ’1’ indicates that the activities the device application carries
out differ from the "out of box" standard configuration. This should not
comprise the configuration of communication.
3- Reserved (0)
4 ... 7 Extended Device Status 0000: Status is "self-testing" or unknown
0001: Firmware update is being carried out
0010: At least one faulty I/O connection
0011: No I/O connections available
0100: Non-volatile configuration is faulty
0101: "Major fault" (bit 10 or 11 is ’1’)
0110: At least one I/O connection is in the "run mode"
0111: At least one I/O connection is available, all are in the "idle
mode"
1000: Reserved
1001: Reserved
1010 ... 1111: Reserved / manufacturer-specific
8 Minor Recoverable Fault The state ’1’ indicates that a "Minor Recoverable Fault" has occurred.
9 Minor Unrecoverable Fault The state ’1’ indicates that a "Minor Unrecoverable Fault" has occurred.
10 Major Recoverable Fault The state ’1’ indicates that a "Major Recoverable Fault" has occurred.
11 Major Unrecoverable Fault The state ’1’ indicates that a "Major Unrecoverable Fault" has occurred.
12 ... 15 Extended Device Status 2 Reserved (0) / manufacturer-specific
Service code
[hex]
Name Description
0x01 Get_Attributes_All Outputs a list of the attributes and the attribute's values for
a certain object.
0x05 Reset Only reset service type ’0’ is supported:
Mains switching (power off/on) is simulated.
0x0E Get_Attribute_Single Outputs the value of a certain attribute.
(Not attribute 10, Heartbeat Interval)