8 I/O data transfer (implicit messages)
51 Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8 I/O data transfer (implicit messages)
To exchange I/O data (implicit messages) between the host system (scanner) and the drive
(adapter), you have to ...
assign the I/O data to the internal port modules in the drive (adapter):
I/O configuration in the »Engineer«
( 55)
configure the I/O data transfer in the host (scanner):
I/O configuration with »RSLogix 5000« version 19 or lower
( 58)
I/O configuration with »RSLogix 5000« version 20 or higher
( 63)
Preconditions for establishing an I/O connection
The data length of the displayed ports in the receive PDO (PDO_RX0) must comply with the
length of the I/O data of the assembly object instance 110 (0x6E, Custom Output) in the
scanner.
The data length of the displayed ports in the transmit PDO (PDO_TX0) must comply with the
length of the I/O data of the assembly object instance 111 (0x6F, Custom Input) in the scanner.
An I/O data object can contain a maximum of 32 mapping entries.
The maximum data length of an I/O data object is 64 bytes