Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17 136
14 Implemented CIP™ objects
14.2 EtherNet/IP objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.2.4 Ethernet Link Object (246 / 0xF6)
The "Ethernet Link Object" provides general information and status information about the Ethernet
interfaces (IEEE 802.3).
Class attributes
Instance attributes
(instance 1 for X233 interface / instance 2 for X234 interface)
Note!
Write accesses to writable attributes become only effective after the device is reset
("Power off/on" or "Type 0 Reset").
Attribute
ID
Service Name Data type Value
1 Get Revision UINT 3 (0x0003)
2 Get Max. Instance UINT 2 (0x0002)
3 Get Number of Instances UINT 2 (0x0002)
Attribute
ID
Service Name Data type Value
1 Get Interface Speed UDINT Current baud rate
• 10 Mbps
• 100 Mbps
2 Get Interface Flags DWORD Status bits of the Ethernet interface
Instance attribute "Interface Flags"
(attribute 2) ( 137)
3 Get Physical Address ARRAY of
USINT[6]
MAC address of the Ethernet interface
6 Set Interface Control STRUCT of:
Control Bits WORD Control bits for the Ethernet interface
Instance attribute "Control Bits"
(attribute 6, Interface Control) ( 138)
Forced Interface Speed UINT Baud rate [in Mbps] at which the Ethernet
interface is to be operated (C13017
/
C14017
).
Example values:
• 10 = 10 Mbps
• 100 = 100 Mbps
10 Get Interface Label SHORT_
STRING
Text for the identification/designation of the
Ethernet interface:
• X233 (instance 1)
• X234 (instance 2)