13 Parameter reference
13.2 Parameters of the communication module for slot MXI1
93
Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13016
C13017
Parameter | Name:
C13016 | Active Multicast IP Address
Data type: UNSIGNED_8
Index: 11559 = 0x2D27
Display of the active multicast IP address
Display range (min. value | unit | max. value)
0 255
Subcodes Info
C13016/1 Multicast IP address (most significant byte)
C13016/2 Multicast IP address
C13016/3 Multicast IP address
C13016/4 Multicast IP address (least significant byte)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13017 | Ethernet Config Control
Data type: UNSIGNED_16
Index: 11558 = 0x2D26
Setting of the baud rate for the Ethernet connections
Depending on the configuration of the Ethernet port of the device to be connected, we recommend the use of a
cross-over cable.
EtherNet/IP connection
( 28)
After changing the setting, carry out a "Type 0 Reset" for the Identity Object (1 / 0x01)
( 121) of the node or
switch off and on the voltage supply of the communication module.
Selection list
0Auto-Negotiation
1 Reserved
2 Reserved
3 Reserved
4 Reserved
5 10 Mbps/Half Duplex
6 10 Mbps/Full Duplex
7 100 Mbps/Half Duplex
8 100 Mbps/Full Duplex
9 Reserved
10 Reserved
11 Reserved
12 Reserved
Subcodes Lenze setting Info
C13017/1 0: Auto-Negotiation Ethernet setting port X233
C13017/2 0: Auto-Negotiation Ethernet setting port X234
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT