Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17 68
8 I/O data transfer (implicit messages)
8.4 I/O configuration with »RSLogix 5000« version 20 or higher
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11. Complete the settings with OK.
The drive is inserted in the configuration tree under the "I/O Configuration".
The corresponding tags are created in the "Controller Tags".
In the example, the drive was named "My_E94AYCEO".
Tag "My_E94AYCEO:I.ConnectionFaulted" for the connection status
Tag set "My_E94AYCEO:I.Data" for the assembly input object instance "111"
Tag set "My_E94AYCEO:O.Data" for the assembly output object instance "110"
If you click "+" before the assembly tag name, all data contained in the assembly tag are
displayed below.
12. The last step is Saving the I/O configuration in »RSLogix 5000«
( 69).