WARNUNG!
▶
UL marking
▶
Suitable for motor group installaon or use on a circuit capable of delivering not more than the rms sym-
metrical amperes (SCCR) of the drive at its rated voltage.
▶
Approved fusing is specied in SCCR tables below.
▶
Marquage UL
▶
Convient pour l'ulisaon sur une installaon avec un groupe de moteurs ou sur un circuit capable de
fournir au maximum une valeur de courant ecace symétrique en ampères à la tension assignée de l'ap-
pareil.
▶
Les disposifs de protecon adaptés sont spéciés dans les SCCR tableaux suivants.
Branch Circuit Protecon (BCP) with Short Circuit Current Rangs (SCCR) with Standard Fuses. (Tested per
UL61800-5-1, reference UL le E132659)
These devices are suitable for motor group installaon when used with Standard Fuses. For single motor
installaon, if the fuse value indicated is higher than 400% of the motor current (FLA), the fuse value has to
be calculated. If the value of the fuse is below two standard rangs, the nearest standard rangs less than
the calculated value shall apply.
Inverter Standard Fuses (UL248) Circuit Breaker (UL489)
Mains kW hp SCCR Max. rated current Class Max. rated current
120 V, 1-ph 0.37 0.50 5 kA 30 A CC, CF, J, T 30 A
120 V, 1-ph 0.75 1.00 5 kA 30 A CC, CF, J, T 30 A
120 V, 1-ph 1.10 1.50 5 kA 30 A CC, CF, J, T 30 A
230 V, 1-ph 0.37 0.50 5 kA 40 A CF, J, T 30 A
230 V, 1-ph 0.55 0.75 5 kA 40 A CF, J, T 30 A
230 V, 1-ph 0.75 1.00 5 kA 40 A CF, J, T 30 A
230 V, 1-ph 1.10 1.50 5 kA 40 A CC, J, T 30 A
230 V, 1-ph 1.50 2.00 5 kA 40 A CC, J, T 30 A
230 V, 1-ph 2.20 3.00 5 kA 40 A CC, J, T 30 A
230 V, 1/3-ph 0.37 0.50 5 kA 40 A CF, J, T 30 A
230 V, 1/3-ph 0.55 0.75 5 kA 40 A CF, J, T 30 A
230 V, 1/3-ph 0.75 1.00 5 kA 40 A CF, J, T 30 A
230 V, 1/3-ph 1.10 1.50 5 kA 40 A CC, J, T 30 A
230 V, 1/3-ph 1.50 2.00 5 kA 40 A CC, J, T 30 A
230 V, 1/3-ph 2.20 3.00 5 kA 40 A CC, J, T 30 A
230 V, 3-ph 3.00 4.00 5 kA 80 A CF, J, T 80 A
230 V, 3-ph 4.00 5.00 5 kA 80 A CF, J, T 80 A
230 V, 3-ph 5.50 7.50 5 kA 80 A CF, J, T 80 A
230 V, 3-ph 7.50 10.00 5 kA 80 A CF, J, T 80 A
230 V, 3-ph 11.00 15.00 5 kA 80 A CF, J, T 80 A
480 V, 3-ph 0.37 0.50 5 kA 30 A CC, CF, J, T 30 A
480 V, 3-ph 0.55 0.75 5 kA 30 A CC, CF, J, T 30 A
480 V, 3-ph 0.75 1.00 5 kA 30 A CC, CF, J, T 30 A
480 V, 3-ph 1.10 1.50 5 kA 30 A CC, CF, J, T 30 A
480 V, 3-ph 1.50 2.00 5 kA 30 A CC, CF, J, T 30 A
480 V, 3-ph 2.20 3.00 5 kA 30 A CC, CF, J, T 30 A
480 V, 3-ph 3.00 4.00 5 kA 63 A CF, J, T 63 A
480 V, 3-ph 4.00 5.00 5 kA 63 A CF, J, T 63 A
480 V, 3-ph 5.50 7.50 5 kA 63 A CF, J, T 63 A
480 V, 3-ph 7.50 10.00 5 kA 63 A CF, J, T 63 A
480 V, 3-ph 11.00 15.00 5 kA 63 A CF, J, T 63 A
Elektrische Installaon
Anschluss nach UL
25