Fusing data
Inverter
kW 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5 11
hp 0.5 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7.5 10 15
Operaon without mains
choke
Fuse
Characterisc gG/gL or gRL
Max. rated current A 40 40 40 40 40 40 80 80 80 80 80
Circuit breaker
Characterisc B
Max. rated current A 32 32 32 32 32 32 80 80 80 80 80
Earth-leakage circuit
breaker
3-phase mains
connecon
≥ 30 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 230/240 V
85