Electrical installaon
Important notes
DANGER!
Electrical voltage
Possible consequences: Death or severe injuries
Any work on the inverter must only be carried out in the deenergised state.
Inverter up to 45 kW: Aer switching o the mains voltage, wait for at least 3 min before you start
working.
Inverter from 55 kW onwards: Aer switching o the mains voltage, wait for at least 10 min before you
start working.
DANGER!
Dangerous electrical voltage
The leakage current against earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences: Death or severe injuries when touching the device in the event of an error.
Implement the measures requested in EN 61800−5−1 or EN 60204−1. Especially:
Fixed installaon
The PE connecon must comply with the standards (PE conductor diameter ≥ 10 mm
2
or use a double PE
conductor)