Residual hazards
Even if notes given are taken into consideraon and protecve measures are implemented, the occurrence
of residual risks cannot be fully prevented.
The user must take the residual hazards menoned into consideraon in the risk assessment for his/her
machine/system.
If the above is disregarded, this can lead to severe injuries to persons and damage to property!
Product
Observe the warning labels on the product!
Hot surface:
Use personal protecve equipment or wait unl the device has cooled down!
Dangerous electrical voltage:
Before working on the product, make sure there is no voltage applied to the power terminals!
Aer mains disconnecon, the power terminals will sll carry the hazardous electrical voltage for the me
given next to the symbol!
High leakage current:
Carry out xed installaon and PE connecon in compliance with:
EN 61800−5−1 / EN 60204−1
Electrostac sensive devices:
Before working on the product, the sta must ensure to be free of electrostac charge!
Motor protecon
With some sengs of the inverter, the connected motor can be overheated.
•
E. g. by longer operaon of self-venlated motors at low speed.
•
E. g. by longer operaon of the DC-injecon brake.
Protecon of the machine/system
Drives can reach dangerous overspeeds.
•
E. g. by seng high output frequencies in connecon with motors and machines not suitable for this
purpose.
•
The inverters do not provide protecon against such operang condions. For this purpose, use
addional components.
Switch contactors in the motor cable only if the controller is inhibited.
•
Switching while the inverter is enabled is only permissible if no monitoring funcons are acvated.
Motor
If there is a short circuit of two power transistors, a residual movement of up to 180°/number of pole pairs
can occur at the motor! (e. g. 4-pole motor: residual movement max. 180°/2 = 90°).
Degree of protecon - protecon of persons and device protecon
•
Informaon applies to the mounted and ready-for-use state.
•
Informaon does not apply to the wire range of the terminals.
-
Terminals that are not wired have low protecon against physical contact.
-
Terminals for large cable cross-secons have lower classes of protecon, e. g. from 15 kW IP10 only.
Safety instrucons
Residual hazards
65