Inverter i550-C75/400-3 i550-C90/400-3 i550-C110/400-3
Rated power kW P
N
90 110 132
Rated power hp P
N
125 150 175
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
without mains choke A I
r, AC
- - -
with mains choke A I
r, AC
135 175 200
Apparent output power kVA A
ON
121 145 171
Rated output current
2 kHz A I
OUT
149 187 216
4 kHz A I
OUT
149 187 216
8 kHz A I
OUT
- - -
16 kHz A I
OUT
- - -
Power loss
2 kHz W 1841 2203 2589
4 kHz W 1961 2348 2760
8 kHz W - - -
16 kHz W - - -
at inverter disablecontroller
inhibit
W 30 30 30
Overcurrent cycle 180 s
Max. output current A I
max, out
186 234 270
Overload me s t
ol
60 60 60
Recovery me s t
re
120 120 120
Max. output current during the
recovery me
A 93 117 135
Overcurrent cycle 15 s
Max. output current A I
max, out
248 312 360
Overload me s t
ol
3 3 3
Recovery me s t
re
12 12 12
Max. output current during the
recovery me
A 93 117 135
Cyclic mains switching 1 me per minute
Brake chopper
Max. output current A I
max, 1
166 333 333
Min. brake resistance Ω R
min
4.7 2.4 2.4
Max. motor cable length shielded
without EMC category m 100 100 100
Category C1 (2 kHz, 4 kHz, 8
kHz)
m - - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 100 100 100
Weight kg 24 35.6 35.6
Weight lb 53 78.5 78.5