Technical data
Rated data
4
l
21
LDEDS−CCU210B EN 4.0
4.2 Rated data
) Note!
The frequency inverter is not suitable for permanent operation in generator
mode.
Mains voltage
Voltage range U
N
3/PE/PEN AC 360 V − 0 % ... 528 V + 0 %
Frequency f
N
45 Hz − 0 % ... 65 Hz + 0 %
Fusing 10 A−T/AC 500 V
Frequency inverter (data for operation on 3/PE/PEN AC 400 V, switching frequency 8 kHz)
Starting current
Effektive I
eff
[A] 4
Peak I
peak
[A] 6
Rated power (typical MOC application)
Operating time 70 % P
N
[kW] 0.75 1.5 −
Operating time 50 % P
N
[kW] − − 2.2
Typical motor power
4−pole asynchronous motor, Y connection
P
N
[kW] − − 2.2
Max. output power S
N
[kVA] 1.3 2.0 3.9
Output current
Duration I
N
[A] 1.8 3.5 5.6
For 60 s I
max
[A] 3.0 5.0 10
Switching frequency
Optionally f [kHz] 2, 4, 8
Lenze setting f [kHz] 8
Motor output frequency f [Hz] 0 ... 120 variable
Power loss at rated load P
V
[W] 22 60 100
Power loss in idle state (only half wave
power, 24V−sensors are not connected)
P
V
[W] 6 6 6
DC motor brake control
Brake voltage
Duration (U = U
N
x 0.45) U [V DC
eff
] 185 (for U
N
= 400 V AC)
Peak (U
peak
= U
N
x Ö2) U
peak
[V DC] 564 (for U
N
= 400 V AC)
Max. braking current I [A
eff
] 0.5 ± 10 %
Integrated switched−mode power supply (supply for external encoders and actuators)
Output voltage U
A
[V DC] +24 (21.6 ... 26.4 V DC)
Max. output current
(current−limited)
I
A
[A DC] 0.5 0.7 0.7
Weight
Control system complete, without counter
plug
[approx. kg] 2.8 3.4 5.0