Function library
Monitoring
I
2
t monitoring
8
l
61
LDEDS−CCU210B EN 4.0
DescriptionPossible settingsCode
SelectionLenzeByte<ñòNo.
C0478 SensoPart:
deceleration ramp Vx ð VLx for
frequency limitation distance in ...
^ 57
1
RW EXT 4
50
1 {Hz/s} 255
... Parameter set 1
2 50 ... Parameter set 2
C0610 R 4
SensoPart: current distance
^ 57
0 {mm} 65535
8.6.2 I
2
t monitoring
By means of the I
2
xt monitoring, the motor utilisation is monitored. The monitoring
simulates a motor protection switch.
How to configure the motor protection switch:
ƒ Enter the rated motor current in C0022.
ƒ Enter the tripping class in C0121.
ƒ Define the response in the case of overload in C0122.
( Stop!
Possible overheating of the motor
The I
2
xt monitoring does not present a full motor protection, as the motor
temperature calculated is reset every time the mains is switched off.
Possible consequences:
ƒ The connected motor can be overheated when the mains is switched on
again if ...
... the motor already is strongly heated and is continued to be overloaded.
... the cooling air supply is interrupted.
... the cooling air is too warm.
Protective measures:
ƒ Provide for a full motor protection that is additionally equipped with a PTC
thermistor or a thermal contact in the motor.
ƒ The PTC thermistor or thermal contact has to be wired and connected
correctly.