INTERBUS 500kBit/s / RS 422
Leuze electronic DDLS 200 25
TNT 35/7-24V
6 INTERBUS 500kBit/s / RS 422
The INTERBUS model of the DDLS 200 has the following features:
Operating ranges 30m, 120m, 200m, 300m, for INTERBUS
Electrically isolated interface
The DDLS 200 is not an INTERBUS participant
Protocol-independent data transmission, transparent compared to other RS 422 protocols
500kBit/s fixed transmission rate with INTERBUS,
with RS 422 generally lower transmission rates as well
Operating range 500m for RS 422 up to 100kBit/s
Cascading of several DDLS 200 is possible (see Chapter 4.3)
6.1 Electrical connection INTERBUS 500kBit/s
The electrical connection to the INTERBUS is made at terminals DO… / DI… and COM as shown in
Figure 6.1.
Figure 6.1: Connection board of the INTERBUS model
ATTENTION!
Please be sure to observe the installation requirements (bus cables, cable lengths,
shielding, etc.) defined in the INTERBUS standard EN 50254
OUT
OUT
WARN
WARN
PE
PE
GND
GND
Vin
Vin
IN
IN
PE
PE
GND
GND
Vin
Vin
SHIELD AREA
SHIELD AREA
BS
BS
A402A
A402A
COM
COM
Tx
Tx
Tx+
Tx+
Rx
Rx
Rx+
Rx+
COM
COM
DI2
DI2
D02
D02
Out
Out
D02
D02
DI2
DI2
COM
COM
D01
D01
DI1
DI1
In
In
DI1
DI1
D01
D01
Bus
Bus
S4
S4
S1
Off
On
IN
INTERBUS - terminals and switches
Terminal Function
DO1 / DI2, Rx+ Receiving line +
DO1 / DI2, Rx– Receiving line –
DI1 / DO2, Tx+ Transmission line +
DI1 / DO2, Tx– Transmission line –
COM Potential equalization
Switch Function
S4 Position In: incoming bus with
shielding connection
via RC element
Position Out (default):
outgoing bus with
direct shielding con-
nection
DDLS200_E.book Seite 25 Mittwoch, 19. Februar 2020 12:22 12