(02/9
MECHANICAL
CHARACTERISTICS
UNITS 860 mm Cabinet
Dimensions (W X D X H) mm 860 X 800 X 1800
Weight (without batteries) kg 140
Battery circuit breaker size Amps 250
Ventilation
Natural
Lifting
Top (via eyes) or bottom (trans-pallet entry)
BATTERY CIRCUIT BREAKER
BOX
N° of
Poles
Suitable for UPS size (kVA)
250 A 3 80 - 120
400 A 4 120
630 A 4 200
800 A 4 300
1000 A 4 400
Undervoltage trip coil rating all units
110Vdc (6,7 9,2 kOhms)
Auxiliary contacts (for signalling) all units
1 set changeover