Setup Inputs
SETUP INPUTS
Setup input of device
Select input to edit
INPUT DEFINITION
1=DEVICE_1 NO-EV-NL-00:01
2=DEVICE_2 NO-AL-L -00:01
3=DEVICE_3 NC-EV-NL-00:01
4=DEVICE_4 NO-AL-L -00:01
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
****************************
NO=NORMALLY OPENED
NC=NORMALLY CLOSED
EV=EVENT
AL=ALARMABLE
NL=NOT LATCHED
L =LATCHED
MIN:SEC=DELAY TIME BEFORE
INPUT WILL TRIGGER
NOTE:EVENT CANNOT BE LATCHED
****************************
>CHANGE LABEL(8 CHARACTERS MAX).
>[DEVICE_1]
>[
>COMMAND SUCCESSFUL
>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)?
>[NO]
>[
>COMMAND SUCCESSFUL
>IS INPUT AN ALARM(AL) OR EVENT(EV)?
>[AL]
>[
>COMMAND SUCCESSFUL
>IS ALARM LATCHED-YES(Y) OR NO(N)?
>[N]
>[
>COMMAND SUCCESSFUL
>DELAY TIME BEFORE TRIGGER (MM:SS)?
>[00:01]
>[
>COMMAND SUCCESSFUL