What to do if Liebert Nfinity UPS shows 'Switch To Manual Bypass'?
- WwatsonsusanSep 16, 2025
If your Liebert Nfinity UPS is on automatic bypass, transfer it to manual bypass.
What to do if Liebert Nfinity UPS shows 'Switch To Manual Bypass'?
If your Liebert Nfinity UPS is on automatic bypass, transfer it to manual bypass.
How to fix Liebert Nfinity 'Reminder alarm - Check air filter'?
If your Liebert UPS displays a reminder to check the air filter, check and clean the fan filter and acknowledge the alarm. This alarm may be disabled, or the interval between these alarms can be configured via the User Interface.
What causes 'Last UPS Shutdown By Emergency Power Off' on Liebert Nfinity UPS?
If your Liebert UPS indicates 'Last UPS Shutdown By Emergency Power Off', it means the REPO switch was pressed. If the REPO switch wasn't pressed, check for REPO wiring problems.
What does 'Battery Cabinet Not Connected' mean on a Liebert Nfinity?
If your Liebert UPS displays 'Battery Cabinet Not Connected', check that the Modular Battery breaker is closed and verify proper connections between the UPS and Modular Battery Cabinet.
What to do if Liebert Nfinity UPS displays 'Battery Test Failure'?
If your Liebert UPS shows a 'Battery Test Failure', replace the battery modules that have active failures or warnings. Depending on the age of the batteries, it may be appropriate to replace all batteries in the system. Schedule a battery test so that the system operation is double-checked once the batteries become fully charged.
How to resolve Liebert Nfinity 'Power Module Not Ready'?
If your Liebert UPS indicates that a 'Power Module Not Ready', ensure that the power module is fully seated and the 1/4 turn fastener is engaged. If the problem persists, replace the power module with a warning or failure condition indicated at the User Interface. If there is no User Interface warning or failure of a power module, look for the power module with LEDs indicating a problem and replace that unit.
How to resolve Liebert Nfinity UPS 'Battery Module Not Ready'?
If your Liebert UPS indicates that a 'Battery Module Not Ready', ensure that the battery module is fully seated and the 1/4 turn fastener is engaged. If the problem persists, replace the battery module with a warning or failure condition indicated at the User Interface. If there is no User Interface warning or failure of a battery module, look for the battery module with LEDs indicating a problem and replace that unit.
What to do if Liebert UPS shows low battery?
If the Liebert UPS displays 'Low Battery', it means the battery power is low. Allow the batteries time to recharge.
How to fix Liebert Nfinity UPS control module not ready error?
If the Liebert UPS indicates 'Control Module not ready,' it means the Control Module is not properly installed. Ensure the lever is in the locked position.
How to fix Liebert Nfinity power module not ready error?
If the Liebert UPS indicates 'Power Module not ready,' it means the Power Module is not properly installed. Ensure the lever is in the locked position.
Covers lethal voltages, working alone, and battery handling, including disposal and shock risks.
Details operating environment, temperature limits, and proper cleaning procedures for optimal performance.
Includes electromagnetic compatibility, IT system type warnings, and precautions for accessing replaceable modules.
Provides an overview of the Liebert Nfinity Power System's purpose, features, and intended use.
Explains the different operational states such as Normal, Back-Up, Auto Restart, Recharge, and Bypass modes.
Details the key physical components of the UPS system, including the frame, modules, and user interface.
Covers inspection, environmental conditions, required setup tools, and site preparation including weight considerations.
Provides step-by-step instructions for safely unloading the UPS from its pallet and securing it in its final location.
Guides on wiring preparation, connecting input/output power cables, and configuring bypass voltage for transformer models.
Information on configuring COM ports and Intellislot ports for system communication and monitoring.
Explains the User Interface Module, its buttons, LEDs, and display for monitoring UPS status.
Step-by-step guides for essential operations like start-up, shutdown, and manual transfer to bypass.
Covers accessing and navigating the Main Menu for UPS Status, Configuration, Logs, Module Replacement, and Tools.
Lists common alarm messages, their potential causes, and recommended corrective actions.
Explains the meaning of the Status and Fault LEDs on Control, Power, and Battery modules for diagnostics.
Provides detailed instructions for safely removing and replacing Control, Power, or Battery modules.
Emphasizes keeping the UPS clean and recommends certified technician services for optimal performance.
Outlines recommended monthly and annual maintenance checks for unit cleanliness, filters, airflow, and module verification.
Instructions for cleaning or replacing air filters on transformer models, noting filter reusability.
Detailed technical data including electrical, mechanical, environmental, input, and output parameters.
Tables showing estimated battery run times based on load and the quantity of internal and external battery modules.