User Manual 10H52192UM60 - Rev. 1 - 09/2011 57
Product Specifications Liebert NX
Chapter 8 Product Specifications
The chapter lists the UPS specifications.
8.1 Conformity and Standards
The UPS has been designed to conform to the European and international standards listed in Table 8-1.
Table 8-1 European and International Standards
Item Normative reference
General and safety requirements for UPS used in operator access areas EN62040-1/IEC62040-1
EMC requirements for UPS EN62040-2/IEC62040-2
Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3
Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN60950), electromagnetic emission and immunity (IEC/EN61000 series), and construction (IEC/EN60146 series and 60529)
8.2 Environmental Characteristics
Table 8-2 Environmental Characteristics
Item Unit
Rated power (kVA)
30 40 60
Noise within 1 m (from the front) dBA 52 54 59
Altitude m
≤
1000, derate power by 1% per 100 m between 1000 m and 2000 m
Relative humidity %RH 0 to 95, non condensing
Operating temperature
°C
0 to 40; battery life is halved for every 10
°C
increase above 20
°C
Storage and transport temperature for UPS
°C
-20 to 70
Recommended battery storage temperature
°C
-20 to 30 (20
°C for optimum battery storage
)
Overvoltage level Overvoltage level 2
Pollution level Pollution level 2
8.3 Mechanical Characteristics
Table 8-3 Mechanical Characteristics
Item Unit
Rated power (kVA)
30 40 60
Dimensions (W
×
D
×
H) mm 600
× 8
43
× 16
00
Weight (excluding battery) kg 230 260 260
Weight (including battery) kg 590 630 630
Color Black ZP7021
Protection degree, IEC(60529) IP20 (front door open or closed)