Carrying out the ENS Test:
Set P0900 to "1" Æ starts the ENS test
P0901 shows the progress of the ENS test
P0908 informs about the frequency ramp (in mHz/s)
P0902 shows the development of the simulated frequency
P0910.00 shows the time measured until the lower frequency limit is reached
P0910.01 shows the time measured until the upper frequency limit is reached
P0903.00 shows the frequency value having caused turnoff at the lower limit
P0903.01 shows the frequency value having caused turnoff at the upper limit
P0909 informs about the voltage ramp (in mV/s)
P0904 shows the development of the simulated voltage
P0910.02 shows the time measured until the lower voltage limit is reached
P0910.03 shows the time measured until the upper voltage limit is reached
P0905.00 shows the voltage value having caused turnoff at the lower limit
P0905.01 shows the voltage value having caused turnoff at the upper limit
ENS test status list:
0 Initializing / ready for start
1 … 3 Frequency test at the lower frequency limit
4 … 6 Frequency test at the upper frequency limit
7 … 9 Voltage test at the lower voltage limit
10 … 12 Voltage test at the upper voltage limit
13 ENS Test completed