44
Carrying out the ENS Test:
• Set P0900 to "1" Æ starts the ENS test
• P0901 shows the progress of the ENS test
• P0908 informs about the frequency ramp (in mHz/s)
• P0902 shows the development of the simulated frequency
• P0910.00 shows the time measured until the lower frequency limit is reached
• P0910.01 shows the time measured until the upper frequency limit is reached
• P0903.00 shows the frequency value having caused turnoff at the lower limit
• P0903.01 shows the frequency value having caused turnoff at the upper limit
• P0909 informs about the voltage ramp (in mV/s)
• P0904 shows the development of the simulated voltage
• P0910.02 shows the time measured until the lower voltage limit is reached
• P0910.03 shows the time measured until the upper voltage limit is reached
• P0905.00 shows the voltage value having caused turnoff at the lower limit
• P0905.01 shows the voltage value having caused turnoff at the upper limit
ENS test status list:
0 Initializing / ready for start
1 … 3 Frequency test at the lower frequency limit
4 … 6 Frequency test at the upper frequency limit
7 … 9 Voltage test at the lower voltage limit
10 … 12 Voltage test at the upper voltage limit
13 ENS Test completed