5.5 List of Fault Messages
Error
code
Error message Description Action
0A0001 Controller voltage 1
Step-up converter of posi-
tive DC link
failed to control
Wait until the controller
has re-stabilized.
0A0002 Controller voltage 2
Step-up converter of nega-
tive DC link
failed to control
Wait until the controller
has re-stabilized.
0A0003 Controller voltage 3 Asymmetry low
Wait until the controller
has re-stabilized.
0A0004 Controller voltage 4 Asymmetry high
Wait until the controller
has re-stabilized.
0A0005 Controller voltage 5
Positive DC link falls below
crest working line voltage
Wait until the controller
has re-stabilized.
0A0006 Controller voltage 6
Negative DC link falls be-
low crest working line volt-
age
Wait until the controller
has re-stabilized.
0A0007 Controller voltage 7
Positive DC link voltage
falls below 90 V
Wait until the controller
has re-stabilized.
0A0008 Controller voltage 8
Positive DC link voltage
exceeds 450 V
Wait until the controller
has re-stabilized.
0A0009 Controller voltage 9
Negative DC link voltage
falls below 90 V
Wait until the controller
has re-stabilized.
0A000A Controller volt. 10
Negative DC link voltage
exceeds 450 V
Wait until the controller
has re-stabilized.
0A000B Controller volt. 11
Positive stepped-up
DC link voltage exceeds
450 V
Wait until the controller
has re-stabilized.
0A000C Controller volt. 12
Negative stepped-up
DC link voltage exceeds
450 V
Wait until the controller
has re-stabilized.
0A000D Line overvoltage
Detecting line
overvoltage
Possibly caused by switch-
ing actions on the net. Re-
measure line voltage.
Service if line voltage is
within normal range
0A000E Line undervoltage
Detecting line
undervoltage
Possibly caused by switch-
ing actions on the net. Re-
measure line voltage.
Service if line voltage is
within normal range
0A000F Overvoltage phase
Detecting line
overvoltage
on outside conductor
Possibly caused by switch-
ing actions on the net. Re-
measure line voltage.
Service if line voltage is
within normal range