47
Error
code
Error message Description Action
0A0010
Undervoltage
phase
Detecting line
undervoltage
on outside conductor
Possibly caused by switch-
ing actions on the net. Re-
measure line voltage.
Service if line voltage is
within normal range
0A0011 Frequency FLL
Detecting a power error
(FLL)
Check system frequency
and line voltage.
Service if system frequency
is within normal range
0A0012 Frequency
Detecting a system fre-
quency error
Check system frequency
and line voltage.
Service if system frequency
is within normal range
0A0013 PV isolation AFISR AFI check
Check insulation of the sys-
tem.
0A0014 No national code
no national code is ad-
justed
Service
0A0100
Power sec error
mess
Error message from power
section
There are further errors.
See error memory.
0A0101 System fault LT1
Unknown fault of power
stack detected
Service
0A0102
Overtemperature
LT1
Overtemperature of the
right part of the heat sink
Allow the unit to cool down.
Acknowledge error
0A0103
Overtemperature
LT2
Overtemperature inside of
the inverter (sensor in the
upper left area)
Allow the unit to cool down.
Acknowledge error
0A0104
Overtemperature
LT3
Overtemperature inside of
the inverter (sensor in the
lower right area)
Allow the unit to cool down.
Acknowledge error
0A0105
Overtemperature
LT4
Overtemperature of the left
part of the heat sink
Allow the unit to cool down.
Acknowledge error
0A0106 Supply voltage LT
Faulty supply voltage at
power section
Service
0A0107 System fault LT7
Unknown fault of power
stack detected
Service
0A0108 Frequency LT
Error of system frequency
of power section
Check system frequency
and line voltage.
Service if system frequency
is within normal range
0A0109 Overvoltage LT
Line overvoltage detector of
power section
Remeasure line voltage
Service if line voltage is
within normal range
0A010A Undervoltage LT
Line undervoltage detector
of power section
Remeasure line voltage
Service if line voltage is
within normal range
0A010B System fault LT11
Unknown fault of power
stack detected
Service