Chapter 13 RS-232C function of K200S MASTER-K
13-6
13.6 Data address structure
This chapter describes how to assign the address of device when performs read / write function.
[ Example of data structure ]
13.6.1 Start of data
The ‘%’ symbol indicates the start of data address. It must be located the start of data
address.
13.6.2 Device type
Device type Device range Remark
P ( I/O relay )
%PW0000 ~ %PW0031 ( 32 words )
%PX0000 ~ %PX031F ( 32 × 16 bits )
Read / Write
M ( auxiliary relay )
%MW0000 ~ %MW0191 ( 192 words )
%MX0000 ~ %MX191F ( 192 × 16 bits )
Read / Write
K ( keep relay )
%KW0000 ~ %KW0031 ( 32 words )
%KX0000 ~ %KX031F ( 32 × 16 bits )
Read / Write
L ( link relay )
%LW0000 ~ %LW0063 ( 64 words )
%LX0000 ~ %LX063F ( 64 × 16 bits )
Read / Write
F ( special relay )
%FW0000 ~ %FW0063 ( 64 words )
%FX0000 ~ %FX063F ( 64 × 16 bits )
Read
T ( timer contact relay ) %TX0000 ~ %TX0255 ( 256 bits ) Read / Write
T ( timer elapsed value ) %TW0000 ~ %TW0255 ( 256 words ) Read / Write
C ( counter contact relay ) %CX0000 ~ %CX0255 (256 bits ) Read / Write
C ( counter elapsed value ) %CW0000 ~ %CW0256 ( 256 words ) Read / Write
S ( step controller ) %SW0000 ~ %SW0099 ( 100 sets ) Read / Write
D ( data register ) %DW0000 ~ %DW4999 ( 5000 words ) Read / Write
% M W 0 1 2 3
Device number
Data type
Device type
Start of data