K300S K1000S Type
Specification
G4F-INTA G3F-INTA
Input points 8 points 16 points
Insulation method Photo coupler insulation
Rated input voltage 24 VDC
Rated input current 10 mA
Operating input voltage 21.6 ~ 26.4 VDC
Max. simultaneously on 1 points / 1COM (100%)
On voltage / current 15 VAC / 6.5 mA
Off voltage / current 5 VDC / 2 mA
Input impedance
About 2.4 kΩ
Off Æ On 0.5 msec or less
Response
time
On Æ Off 0.5 msec or less
Common 1 points / 1 com
Internal current consumption 65 mA 200 mA
Operation indicator LED display
External wiring
20 points terminal block connector
( M3×6 screw )
38 points terminal block connector
( M3×6 screw )
Weight 160 g 400 g