Chapter 7 I/O modules MASTER-K
7-31
7.4 Digital input / output hybrid modules
7.4.1 8 points 12/24VDC input + 8 points relay output
K200S
G6H-DR2A
Input Output
Input point 8 points Output points 8 points
Insulation method Photo coupler insulation Insulation method Relay insulation
Rated input voltage DC12 / 24V Rated load voltage / current
24 VDC / 2A (resistive load),
220 VAC / 2A (cosψ = 1)
Rated input current 3 / 7 mA Min. load voltage / current DC5V / 1 mA
Operating voltage DC10.2~26.4V Max. load voltage / current AC250V, DC125V
Max. simultaneously
on
100% simultaneously on Leakage current 0.1 mA (AC220V, 60Hz)
On voltage / current 9.5 VDC / 3.0 mA Max. switching frequency 1.200 times / hour
Off voltage / current 5 VDC / 1.5 mA Surge absorber None
Input impedance
About 3.3 kΩ
Mechanical
Off Æ On 5 ms or less
Lifetime of
contact
Electrical
Same as G6Q-RY2A
Respo
nse
time
On Æ Off
7 ms or less
Off On
10 ms or less
Common
8 points / 1COM
Response
time
On Off
12 ms or less
- - Common 8 points / 1COM
Operation Indicator LED
External wiring 18 points terminal block connector (M3×6 screw)
Internal current
consumption
250 mA
Weight 0.20 kg
Wiring
0
1
2
3
4
5
6
7
08
L
09
0
A
0B
0C
0D
0E
0F

Table of Contents