Chapter 16 Built-in high speed counter of K200S MASTER-K
16-6
16.5.2 Operation mode (D4999)
Input terminal
Operation mode
A phase B phase Preset
Multipli-
cation
Description
h1000
Pulse
input
– – –
U/D : Set by sequence program
PR : Set by sequence program
h1010
Pulse
input
–
Preset
input
–
U/D : Set by sequence program
PR : Set by preset input
h1100
Pulse
input
U/D
input
– –
U/D : Set by U/D input
PR : Set by sequence program
1
phase
h1110
Pulse
input
U/D
input
Preset
input
–
U/D : Set by U/D input
PR : Set by preset input
h2001
A-phase
input
B-phase
input
– 1
PR : Set by sequence program
1 multiplication
h2002
A-phase
input
B-phase
input
– 2
PR : Set by sequence program
2 multiplication
h2004
A-phase
input
B-phase
input
– 4
PR : Set by sequence program
4 multiplication
h2011
A-phase
input
B-phase
input
Preset
input
1
PR : Set by preset input
1 multiplication
h2012
A-phase
input
B-phase
input
Preset
input
2
PR : Set by preset input
2 multiplication
2
phase
h2014
A-phase
input
B-phase
input
Preset
input
4
PR : Set by preset input
4 multiplication
The U/D and PR input of sequence prog
ram must be programmed with dummy input even
they are set as external input. When the PR and/or U/D is set as external input, the input
conditions of sequence program is ignored.